PURPOSE
These heat-shrinkable cable joints are designed to be applied to branching or separating from the main power line of single-core screened plastic cables types XHP, XHE and cables of similar construction at an angle of 90 degrees (T joint) and 150 degrees (Y joint).

CONSTRUCTION
Fixing these joints is realized by using T and Y connectors that come in the joint kit. Electrical field regulation is realized by stress control elements, and screen joining is made by using semiconducting tapes. Joint insulation is realized by coiling of insulating tape. Earth wire joint is made by using connectors and copper wire mesh, while water resistance and mechanical protection are achieved by heat-shrinkable tubes with hot melting adhesive and sealing tape.
Code No. Type of product Voltage level (kV) Conductor cross- section
(mm2)
Lenght of joint L
(mm)
14022 TSKS 10/1-70-T 10 35 - 70 800
14023 TSKS 10/1-150-T 10 95 - 150 800
14024 TSKS 20/1-70-T 20 35 - 70 850
14025 TSKS 20/1-150-T 20 95 - 150 850
14026 TSKS 10/1-70-Y 10 35 - 70 750
14027 TSKS 10/1-150-Y 10 95 - 150 750
14028 TSKS 20/1-70-Y 20 35 - 70 800
14029 TSKS 20/1-150-Y 20 95 - 150 800